Power & UPS

Power budget & UPS sizing

From a router under the stairs to a full server rack. List the kit, pick the UPS you have or are looking at, and see the load, how long it will hold up, what it costs to run, and how much heat it gives off.

Equipment

DeviceQtyWatts eachTotal W

Typical figures are average running loads, not the PSU nameplate (a 750 W server PSU rarely draws 750 W). Use measured or datasheet figures where you have them. List PoE devices (APs, cameras, phones) as their own rows: a PoE switch's base figure doesn't include them.

UPS

Battery chemistry & inverter losses

Idle overhead is the power the UPS uses to run itself (inverter, fans, electronics). It stays the same whatever you plug in. Example: a UPS using 40 W itself, with 50 W of kit plugged in, spends almost half its battery on itself; with 1,000 W plugged in, the same 40 W is only about 4% of the drain. Online units have more overhead than line-interactive ones. Changing the topology or rating resets these to typical values.

Assumptions

Modern IT power supplies run at a power factor of about 0.95–0.99. Older or cheap adaptors can be nearer 0.6.